Second Mate Orals: Fire-Fighting Appliances (SOLAS Chapter II-2) – 12 Questions
Fire-fighting appliances are a favourite area for surveyors in the Second Mate (FG) oral exam. You may be asked how many fire pumps your last ship had, what is inside a fire-fighter’s outfit, or how you would flood a cargo hold with CO2. This set covers the questions candidates are asked most often, with short model answers and the SOLAS or FSS Code rule behind each one.
How to use this set: read each question, answer it aloud as you would in front of the surveyor, then open the model answer to check yourself.
Questions and model answers
Q1. What are the classes of fire, and which extinguishing agent suits each?
Class A: ordinary solid combustibles such as wood, paper, cloth and rope – water (cooling) is best. Class B: flammable liquids such as fuel oil, lube oil and paint – foam, dry powder or CO2 (smothering). Class C: flammable gases – stop the gas flow first; dry powder can knock down the flame. Class D: burning metals – special dry powder only, never water. Many ships also mark galley extinguishers for cooking oil fires (Class F in the European system). Live electrical fires are fought with CO2 or dry powder after isolating the supply; never use a water jet on live equipment.
Reference: ISO 3941 / EN 2 fire classification; ship’s Fire Safety Training Manual (SOLAS II-2/15.2.3)
Q2. How many fire pumps must a cargo ship carry, and what pressure must be kept at the hydrants?
A cargo ship of 1,000 gross tonnage and upwards must have at least two independently driven fire pumps. Below 1,000 GT, at least two power-driven pumps, one of which must be independently driven. With two pumps delivering water through adjacent hydrants, the minimum pressure at all hydrants is 0.27 N/mm² for cargo ships of 6,000 GT and upwards, and 0.25 N/mm² below 6,000 GT. The maximum pressure must not exceed that at which a fire hose can still be controlled. In a cargo ship the total required capacity of the main fire pumps need not exceed 180 m³/h, and each main fire pump should give at least 25 m³/h.
Reference: SOLAS II-2/10.2.1.6 and 10.2.2
Q3. When is an emergency fire pump required on a cargo ship, and what must it deliver?
If a fire in any one compartment could put all the main fire pumps out of action, the cargo ship must have another means of supplying water – normally a fixed, independently driven emergency fire pump located outside the machinery space. Its capacity must be at least 40% of the total capacity of the required fire pumps, and not less than 25 m³/h for cargo ships of 2,000 GT and upwards (15 m³/h below 2,000 GT). It must be able to supply two jets of water. Its power source, sea suction and starting arrangements must be independent of the space containing the main fire pumps, and it must start easily even when cold.
Reference: SOLAS II-2/10.2.2.3; FSS Code Chapter 12
Q4. What are the rules for fire hoses and nozzles on a cargo ship?
Fire hoses must be at least 10 m long but not more than 15 m in machinery spaces, 20 m in other spaces and open decks, and 25 m on open decks of ships with a maximum breadth over 30 m. A cargo ship of 1,000 GT and upwards carries one hose for each 30 m of the ship’s length plus one spare, but never fewer than five in all. Each hose has a nozzle and the couplings needed; unless every hydrant has its own hose and nozzle, couplings and nozzles must be fully interchangeable. Standard nozzle sizes are 12 mm, 16 mm and 19 mm, and nozzles must be an approved dual-purpose (jet/spray) type with a shut-off.
Reference: SOLAS II-2/10.2.3
Q5. What is the international shore connection? Give its main dimensions.
It is a standard flange that lets a shore fire brigade or another ship pump water into your fire main, even if the hose threads do not match. Ships of 500 GT and upwards must carry at least one. One side has a flat face; the other has a coupling that fits the ship’s hydrants and hoses. Dimensions: outside diameter 178 mm, inside diameter 64 mm, bolt circle 132 mm, four 19 mm slotted holes, flange thickness at least 14.5 mm. It is kept with a gasket suitable for 1.0 N/mm², four 16 mm bolts 50 mm long, four nuts and eight washers. Facilities must allow it to be used on either side of the ship.
Reference: SOLAS II-2/10.2.1.7; FSS Code Chapter 2
Q6. State the main requirements for portable fire extinguishers.
Ships of 1,000 GT and upwards carry at least five portable extinguishers. Each powder or CO2 extinguisher must hold at least 5 kg and each foam extinguisher at least 9 litres, and a portable extinguisher must not weigh more than 23 kg. One of the extinguishers meant for a space is stowed near its entrance. CO2 extinguishers are not placed in accommodation spaces. Spare charges are carried for 100% of the first ten extinguishers and 50% of the rest (not more than 60 in total); for extinguishers that cannot be recharged on board, extra ready-to-use extinguishers are carried instead.
Reference: SOLAS II-2/10.3; FSS Code Chapter 4
Q7. What does a fire-fighter’s outfit contain, and how many must a cargo ship carry?
Personal equipment: protective clothing, boots and gloves, a rigid helmet, an approved electric safety lamp with at least 3 hours’ burning time (explosion-proof on tankers), and an axe. Breathing apparatus: a self-contained compressed-air set with at least 1,200 litres of air or at least 30 minutes’ use, fitted with an alarm that warns the wearer before the air runs low. Each set has a fireproof lifeline at least 30 m long. All ships carry at least two outfits and tankers two more. Two spare cylinders are carried for each set (one if the ship can recharge cylinders on board). Ships also carry at least two explosion-proof or intrinsically safe two-way portable radios for each fire party.
Reference: SOLAS II-2/10.10; FSS Code Chapter 3
Q8. What is an EEBD? Can you use it to fight a fire?
An Emergency Escape Breathing Device supplies air or oxygen only to escape from a space with a dangerous atmosphere. It must last at least 10 minutes and has a hood or full face piece to protect the eyes, nose and mouth. It must not be used for fire-fighting, for entering oxygen-deficient spaces or tanks, or by fire-fighters. A cargo ship keeps at least two EEBDs within the accommodation plus one spare, and further EEBDs in the machinery spaces at places that are easy to reach during an escape.
Reference: SOLAS II-2/13.3.4 and 13.4.3; FSS Code Chapter 3; MSC/Circ.1081
Q9. How much CO2 must be carried for cargo holds and machinery spaces, and how fast must it discharge?
Cargo spaces: enough CO2 to give free gas equal to at least 30% of the gross volume of the largest cargo space protected. In container and general cargo spaces at least two-thirds of the gas must reach the space within 10 minutes; in solid bulk cargo spaces within 20 minutes. Machinery spaces: free gas equal to the larger of 40% of the gross volume of the space (excluding the casing) or 35% including the casing, and 85% must be discharged within 2 minutes. Free gas is calculated at 0.56 m³ per kg of CO2.
Reference: FSS Code Chapter 5, paragraph 2.2.1
Q10. A fire is reported in No. 3 cargo hold. How would you use the fixed CO2 system?
Raise the alarm and inform the Master. Confirm which hold is on fire. Make sure nobody is in the hold and take a head count at the muster station. Stop the hold ventilation and close all ventilators, hatches and other openings to make the space as airtight as possible. Then, on the Master’s order, release CO2 into that hold only, using the number of cylinders shown in the ship’s CO2 operating instructions. Fixed CO2 systems have two separate controls – one opens the valve to the protected space, the other releases gas from the cylinders. For spaces where people normally work, such as machinery spaces, ro-ro spaces and reefer container holds, opening the release cabinet sounds a pre-discharge alarm for at least 20 seconds before the gas is released. Afterwards, keep the hold closed, monitor boundary temperatures, and do not open it until advised, as the fire can re-ignite when air gets in.
Reference: FSS Code Chapter 5, paragraphs 2.1.3 and 2.2.2; ship’s CO2 operating instructions
Q11. What types of fire detector are fitted on ships, and when must they operate?
Smoke detectors, heat detectors and flame detectors, together with manual call points, all feeding a fixed fire detection and alarm panel. Smoke detectors in stairways, corridors and escape routes must operate before smoke density exceeds 12.5% obscuration per metre, but not until it exceeds 2%. Heat detectors must operate before the temperature exceeds 78°C but not until it exceeds 54°C, when the temperature rises at less than 1°C per minute. Cargo holds are often protected by a sample extraction smoke detection system, which draws air from each hold to a detector unit.
Reference: SOLAS II-2/7; FSS Code Chapters 9 and 10
Q12. What are the requirements for the fire control plan, the training manual and fire drills?
The fire control plan, showing control stations, fire sections, detection and alarm systems, extinguishing appliances, means of access and ventilation controls for each deck, is permanently exhibited for the officers and kept up to date. A duplicate set (or booklet) is stored in a prominently marked weathertight enclosure outside the deckhouse for shore fire-fighters. A fire safety training manual, in the working language of the ship, is kept in each crew mess room and recreation room or in each crew cabin. Every crew member must take part in at least one fire drill a month; if more than 25% of the crew have not taken part in a drill on that ship in the previous month, a drill is held within 24 hours of leaving port. Drills are recorded in the log book.
Reference: SOLAS II-2/15.2.3 and 15.2.4; SOLAS III/19.3 and 19.5
Quick self-test
Choose your answer, then tap “Show answer” to check.
1. The minimum hydrant pressure on a cargo ship of 8,000 GT is: (a) 0.25 N/mm² (b) 0.27 N/mm² (c) 0.30 N/mm² (d) 0.40 N/mm²
Answer: (b) 0.27 N/mm² for cargo ships of 6,000 GT and upwards (SOLAS II-2/10.2.1.6).
2. The outside diameter of the international shore connection flange is: (a) 132 mm (b) 150 mm (c) 178 mm (d) 215 mm
Answer: (c) 178 mm; 132 mm is the bolt circle (FSS Code Chapter 2).
3. The minimum service duration of an EEBD is: (a) 5 minutes (b) 10 minutes (c) 15 minutes (d) 30 minutes
Answer: (b) At least 10 minutes, and it is for escape only (FSS Code Chapter 3).
4. The CO2 carried for cargo spaces must give free gas equal to at least what share of the gross volume of the largest cargo space? (a) 20% (b) 30% (c) 35% (d) 40%
Answer: (b) 30% of the gross volume of the largest cargo space protected (FSS Code Chapter 5).
5. Portable fire extinguishers and their propellant cartridges must be hydrostatically tested: (a) every year (b) every 2 years (c) every 5 years (d) every 10 years
Answer: (d) Every 10 years; in addition, at least one extinguisher of each type and year of manufacture is test-discharged every 5 years, often during a fire drill (MSC.1/Circ.1432).
Disclaimer: These questions and model answers are study aids written by CrewMirror, not official examination questions or answers. Please check the current text of SOLAS, the FSS Code and the latest DGMA examination requirements before your exam. CrewMirror and its owners and operators will not be responsible for any loss or damage caused by the use of information published on CrewMirror pages and posts.