Second Engineer Orals: Refrigeration and Air Conditioning – 12 Questions

Refrigeration and air conditioning come up often in the Second Engineer (MEO Class II) oral exam, because the provision plant and the AC plant are usually the Second Engineer’s responsibility on board. The surveyor wants to see that you understand the cycle, can read the plant’s pressures and temperatures, and know how to deal with common faults safely and legally. This set covers the questions candidates are asked most often, with short model answers.

How to use this set: read each question, answer it aloud as you would in front of the surveyor, then open the model answer to check yourself.

Questions and model answers

Q1. Explain the vapour compression refrigeration cycle.

The compressor draws low-pressure refrigerant vapour from the evaporator and compresses it to a high pressure and temperature. In the condenser, cooled by sea water or fresh water, the hot vapour gives up its heat and condenses into liquid, which collects in the receiver. The high-pressure liquid then passes through the expansion valve, where its pressure drops and part of it flashes off, so it enters the evaporator as a cold, low-pressure mixture. In the evaporator (the cooling coil in the room) the liquid boils by taking heat from the room air, and leaves as vapour to return to the compressor. So the plant has a high-pressure side (compressor discharge to expansion valve) and a low-pressure side (expansion valve to compressor suction).

Q2. How does a thermostatic expansion valve work, and what is superheat?

Superheat is the difference between the actual temperature of the vapour at the evaporator outlet and the saturation (boiling) temperature at the evaporator pressure. The thermostatic expansion valve has a sensing bulb clamped to the evaporator outlet pipe. If the outlet gets warmer (more superheat), the bulb pressure rises and opens the valve to feed more liquid; if the superheat falls, the valve closes down. In this way it keeps the evaporator well fed while making sure only dry vapour, not liquid, returns to the compressor. The superheat setting is adjusted as per the maker’s instructions.

Q3. What is sub-cooling and why is it useful?

Sub-cooling means cooling the condensed liquid below its saturation temperature at condenser pressure. It is useful for two reasons: each kilogram of liquid can absorb more heat in the evaporator, so the refrigerating effect increases; and the liquid is less likely to flash into vapour in the liquid line before the expansion valve, which would reduce the valve’s capacity and cause poor cooling.

Q4. What safety devices are fitted on a refrigeration compressor?
  • High-pressure cut-out: stops the compressor if discharge pressure is too high, for example on cooling water failure, a dirty condenser, air in the system or overcharge. It is normally reset by hand after finding the cause.
  • Low-pressure cut-out: stops the compressor on low suction pressure, for example on refrigerant shortage, a choked drier or expansion valve, or an iced-up evaporator. It is also often used for normal start/stop control.
  • Oil pressure (differential) cut-out: stops the compressor if lubricating oil pressure is too low, usually after a short time delay to allow pressure to build up on starting.
  • Relief valve or bursting disc: protects the compressor or condenser against excessive pressure if the cut-out fails.
  • Others: motor overload protection and, on many plants, a high discharge temperature cut-out.
See also  Second Engineer Orals: Air Compressors and Starting Air System – 11 Questions
Q5. How will you know the plant is short of refrigerant, and how do you find a leak?

Signs of shortage are: bubbles or a half-empty view in the liquid line sight glass; low suction pressure and low discharge pressure; high superheat at the evaporator outlet; the compressor running for long periods or tripping on low pressure; and room temperatures that are slow to come down. To find the leak, use an electronic leak detector or soap solution on joints, valve glands, flare fittings and the condenser. On a sea-water-cooled condenser, a tube leak may show as refrigerant in the cooling water outlet. Repair the leak first; topping up without repairing only wastes refrigerant and harms the environment.

Q6. What are the signs of air in the system, and how do you remove it?

Air does not condense, so it collects at the top of the condenser. The main sign is a condenser pressure higher than the saturation pressure corresponding to the condensing temperature, along with high discharge temperature, possible high-pressure trips and poorer cooling. To remove it, stop the compressor, keep cooling water running so the refrigerant condenses and the air gathers at the top of the condenser, then purge the air from the purge valve at the top, using a recovery unit as required by your company’s procedures so that refrigerant is not released. Then find how the air got in, for example a leak on the suction side when it was working below atmospheric pressure, or poor evacuation after maintenance.

Q7. What harm does moisture do in a refrigeration system, and how is it removed?

Moisture can freeze at the expansion valve orifice and block it on and off, giving erratic cooling. It also reacts with the refrigerant and oil to form acids and sludge, which corrode parts, damage motor windings in hermetic and semi-hermetic compressors and break down the oil. Synthetic (POE) oils used with HFC refrigerants absorb moisture easily, so they must be kept sealed. Moisture is shown by the colour of the moisture indicator in the sight glass. It is removed by the filter drier in the liquid line, which should be changed when moisture is shown; if a lot of moisture has entered, the system must be evacuated with a vacuum pump before recharging.

Q8. How do you charge refrigerant into the plant?

First confirm the correct refrigerant and that the leak has been repaired. A common shipboard method is liquid charging: connect the cylinder to the charging valve in the liquid line after the receiver, purge the charging line of air, close the receiver outlet valve and run the compressor so that liquid is drawn in from the cylinder. Watch the sight glass and the pressures, stop when the sight glass is clear and conditions are normal, then reopen the receiver outlet valve. Zeotropic blends such as R407C and R404A must be charged as liquid, because charging vapour would change the blend’s composition. Weigh the cylinder before and after so the quantity is known and can be recorded, and do not overcharge, since that floods the condenser and raises discharge pressure.

Q9. What is liquid flooding (slugging) of the compressor, and how is it prevented?

Liquid refrigerant reaching the compressor cannot be compressed and can break valves, gaskets and connecting rods. It also dilutes the oil and causes oil foaming when the crankcase pressure drops on starting, which leads to loss of lubrication. Causes include an expansion valve stuck open or with too low a superheat setting, a loose sensing bulb, an iced evaporator or failed evaporator fan, and refrigerant migrating into the crankcase while the compressor is stopped. Prevention: correct superheat setting, sensing bulb well clamped and insulated, regular defrosting, the crankcase heater in use when the compressor is stopped, and a pump-down before stopping where the plant is designed for it.

See also  Second Engineer Orals: Turbochargers and Surging – 11 Questions
Q10. Why must evaporators be defrosted, and how is it done?

In freezing rooms, moisture from the air forms frost on the evaporator coil. Frost acts as insulation and blocks air flow, so the room temperature rises, suction pressure falls and liquid may return to the compressor. Defrosting is usually done automatically by a timer, using electric heaters on the coil and drain tray, or by passing hot gas from the compressor discharge through the evaporator. During defrosting the liquid supply to that room is shut off and the fans are stopped, and the drain line must be kept clear and heated so that melt water drains away instead of freezing.

Q11. What does MARPOL Annex VI say about refrigerants?

Regulation 12 deals with ozone-depleting substances (ODS) such as CFCs, halons and HCFCs (for example R22). Deliberate emissions of ODS are prohibited, including during maintenance, repair and disposal, apart from minimal releases during recovery or recycling. New installations containing ODS other than HCFCs are prohibited on ships built on or after 19 May 2005 (and as new installations on existing ships from that date), and installations containing HCFCs are prohibited on ships built on or after 1 January 2020 (with the same rule for new installations on existing ships). Each ship must keep a list of equipment containing ODS, and a ship with rechargeable ODS systems must keep an ODS Record Book with entries in kilograms for recharging, repair, discharge to the atmosphere, delivery to reception facilities and supply to the ship. Removed ODS and equipment must go to proper reception facilities. HFCs such as R134a, R404A and R407C do not deplete ozone, but they are strong greenhouse gases, so they must not be vented either; recover them as per your company’s procedures.

Reference: MARPOL Annex VI, Regulation 12

Q12. How does a ship’s air conditioning plant control temperature and humidity?

In the air handling unit, a mix of fresh air and recirculated air is drawn through filters by a fan. In hot weather it passes over the cooling coil (a direct-expansion evaporator or a chilled water coil), which cools it below its dew point so that moisture condenses and drains away, lowering the humidity. If the air becomes too cold, it can be reheated slightly before being sent to the cabins. In cold weather the air is warmed by a steam or hot water heating coil, and a humidifier adds moisture, because heated air becomes very dry. Thermostats and humidity controllers adjust the coils, and the supply is distributed through trunking to the accommodation. Clean filters, clear condensate drains and clean coils are important both for performance and for health on board.

Quick self-test

Choose your answer, then tap “Show answer” to check.

1. In a correctly working plant, refrigerant leaves the evaporator as: (a) sub-cooled liquid (b) slightly superheated vapour (c) high-pressure liquid (d) high-pressure vapour
See also  Second Engineer Orals: Scavenge Fires – 11 Questions

Answer: (b) The expansion valve keeps a little superheat so only dry vapour returns to the compressor.

2. Bubbles in the liquid line sight glass with low suction pressure and high superheat usually mean: (a) overcharge (b) air in the system (c) shortage of refrigerant (d) too much oil

Answer: (c) These are the classic signs of a refrigerant shortage.

3. Air in the system is shown by: (a) low suction pressure (b) condenser pressure higher than the saturation pressure for the condensing temperature (c) frost on the suction line (d) a wet moisture indicator

Answer: (b) Air adds its own pressure in the condenser, so the pressure is higher than the refrigerant alone would give.

4. Under MARPOL Annex VI Regulation 12, installations containing HCFCs are prohibited on ships constructed on or after: (a) 19 May 2005 (b) 1 January 2015 (c) 1 January 2020 (d) 1 January 2030

Answer: (c) 1 January 2020; other ODS were banned for new installations from 19 May 2005.

5. A zeotropic blend such as R407C should be charged: (a) as vapour into the suction (b) as liquid (c) either way, it makes no difference (d) only after draining the oil

Answer: (b) As liquid, so the blend’s composition does not change.

Disclaimer: These questions and model answers are study aids written by CrewMirror, not official examination questions or answers. Always follow your equipment maker’s instructions and your company’s procedures, and check the current MARPOL and classification society requirements and the latest DGMA examination requirements before your exam. CrewMirror and its owners and operators will not be responsible for any loss or damage caused by the use of information published on CrewMirror pages and posts.

Looking for a job at sea? Find the latest maritime vacancies and apply to companies of your choice on WhatsApp with WhatsMate.

This article was prepared with the help of Internet Search and AI assistance tools.